Analysis of On-Line Partial Discharge Patterns in High Voltage Motor Stator Windings

고압전동기 고정자 권선의 운전중 부분방전 패턴 분석

  • Published : 2003.07.21

Abstract

During normal machine operation, partial discharge(PD) measurements were performed with turbine generator analyzer(TGA) in two high voltage motors. Two 6.6kV motors were installed with 80pF capacitive couplers at the terminal box. The PD patterns were displayed two dimensional and three dimensional. TGA summarizes each plot with two quantifies such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). Off-line PD measurements were conducted on one 4.16kV motor. The motor was energized to 2.4kV, 3.0kV, 3.5kV and 4.16kV, respectively. The PD levels in pC were measured with a conventional digital PD detector. The comparison of positive to negative PD indicates whether the defect elements of PD are within the insulation or on the insulation surface. Discharge at conductor surface was discovered in No. 1 motor. Internal discharges were generated in phase A, B and C of No. 2 motor, Slot discharges occurred in three phases of No. 3 motor.