Insulation Ageing Diagnosis Using HFPD Pattern Analysis

HFPD 패턴분석을 이용한 절연열화 진단

  • Published : 2003.07.21

Abstract

The aging diagnosis method using partial discharge measurement detects discharge signals that critical cause of failure in insulation material operated a long time and can diagnose aging state of insulation materials with an aging analysis algorithm. The HFPD measurement method is a technique to analyze aging state of high voltage insulation materials and detect higher frequency signals than conventional PD measurement method therefore it takes less noise effect and could execute active line measurement. It is possible to analyze main discharge phenomena and obtain access to aging progress occurred in insulation materials through accumulation of HFPD signals during determined interval and expression of fractal dimension using statistical process of accumulated signals. The HFPD signals that occurred in each applied voltages are measured during 180 cycles and accumulated to the same phase of one cycle. These patterns that made by previous method are normalized with logarithm function and than inputted to neural networks. The aging diagnosis of insulation material was possible and the recognition ratio of neural network appeared very high.

Keywords