Analysis of Insulation Condition in High Voltage Motor Model Coils

고압전동기 모델 코일의 절연상태 분석

  • Published : 2003.07.21

Abstract

80pF capacitive couplers were connected to six 6.6kV motor model coil terminals. The voltage applied to the coils were 3.81kv, 4.76 kV and 6.6kV, respectively. These stator coils have various types of artificial insulation defects such as large voids, semi-conductive coating damage and strand insulation fault. Digital PD detector(PDD) and turbine generator analyzer(TGA) were used to measure PD activity. TGA summarizes each plot with two quantities such as the normalized quantity number(NQN) and the peak PD magnitude(Qm). The PD levels in PD were measured with a conventional digital PD detector. Most of the defect mechanism of large motor stator winding can be associated with PD patterns such as internal and slot discharges. PD patterns coincide with PDD and TGA. These instruments have an input bandwidth of 40-400kHz and 0.1-350MHz. Surge testing detects faults in inter-turn winding of high voltage motor model coils.