용수 재이용을 위한 소규모 하수처리시설의 UV disinfection system
Feasibility Study of UV Disinfection system of Small Wastewater System for Water Reclamation
- 발행 : 2002.10.12
초록
Deterministic and probabilistic approaches to the design of ultraviolet (UV) disinfection system for water reclamation are reviewed and discussed. The high inactivation of TC, FC and E. coli by UV disinfection was demonstrated and the inactivations of TC, FC and E. coli were 97%, 98% and 99%, respectively. Within the range of 0.3-4.5mWs/cm, the effect of UV does on the inactivation ratio was not observed. However, in the highest wattage of UV lamp, 39W, the inactivation ratio of TC, FC and E. coli was 100%, regardless of the UV does so the UV density was more effective on inactivation ratio of TC, FC and E. coli rather than UV does. Under the 0.4 mWs/cm and 16W of UV lamp, the effect of dissolved organic matter and turbidity on the inactivations of TC, FC and E. coli could not be observed in this study within the range of 0-60mg/L and 0-40 NTU respectively.