Performance Verification of Gas Insulated Switchgear using UHF Partial Discharge Diagnosis Method

UHF법 부분방전 진단기법에 의한 가스절연 개폐장치의 성능검증

  • 김정배 ((주) 효성 중공업 연구소) ;
  • 박경수 ((주) 효성 중공업 연구소) ;
  • 송원표 ((주) 효성 중공업 연구소) ;
  • 김덕수 ((주) 효성 중공업 연구소) ;
  • 김종화 (한국전력공사 송변전 건설처)
  • Published : 2002.11.09

Abstract

UHF method is very effective to diagnosis for partial discharge of GIS. In generally, inner UHF sensor can be attached on sheath cover of GIS under construction for periodic inspection. However, there is no inner UHF sensor for GIS of the domestic substation. We used the outer UHF sensor attached on spacer for GIS of existing substation. In this paper, we report the diagnosis result of partial discharge on 800kV GIS in domestic substation. From these results, we can find the quantity, reason and location of PD and certificate the performance of UHF method for partial discharge diagnosis of GIS.