대한전기학회:학술대회논문집 (Proceedings of the KIEE Conference)
- 대한전기학회 2002년도 추계학술대회 논문집 전력기술부문
- /
- Pages.161-163
- /
- 2002
광역정전 복구를 위한 시송전 계통 분석시스템 개발
Development of the Primary Restorative Transmission System Analyser to Restore Massive Blackout
- Lee, Nam-Ho (Korea Electric Power Research Institute) ;
- Song, In-Jun (Korea Electric Power Research Institute) ;
- Kim, Kyeong-Ho (Korea Electric Power Research Institute) ;
- Ghoo, Jin-Boo (Korea Electric Power Research Institute)
- 발행 : 2002.11.15
초록
Service restoration following a complete or partial collapse starts with reenergizing a transmission line from black-start generators. Voltage problems can arise from Ferranti effect as unloaded transmission line is reenergized. This Paper presents system analyser to develop for verifying the primary restorative transmission system. The algorithm which has been used in the analyser is to handle load pick-up compensating Ferranti effect. and terminal voltage and reactive capability limitation of black-start generators about self-excitation.
키워드