An experimental study on the characteristics of Gifford-McMahon cryocooler

Gifford-McMahon 극저온 냉동기의 특성에 관한 실험적 연구

  • Published : 2002.02.01

Abstract

To achieve good cryogenic circumstances by Gifford-McMahon cryocooler, we have to constitute optimal conditions with various factors for G-M cryocooler. In this study, cool-down characteristics were presented with some factors using brass matrix mesh (1st stage) and Pb ball (2nd stage) as regenerator materials for the heat exchangers. The effects of the variations of Helium gas pressure and cycle frequency on the cooling capacity of G-M cryocooler are investigated experimentally. The presented results could be summarized as follows : 1) As the steady state pressure increases, 'no load temperature' decreases but cooling capacity increases. 2) It is confirmed that the characteristics of the specific heat of the regenerator materials agree well with the cool-down characteristics of 10 K cryocooler.

Keywords