Conceptual Design of Terminal Cryostat for HTS Power Cable

고온초전도 전력케이블 단말 저온조의 개념 설계

  • Published : 2002.02.01

Abstract

The model of terminal cryostat for HTS power cable is conceptually designed. In this paper we defined that heat loads of the terminal cryostat was only cooled by the liquid nitrogen without cooling gas. Total heat loss calculated by analytical and numerical methods are 46.4W at 0A and 69W at 1260A for the 3-Phase HTS power cable system of 50MW, 22.9kV.