Correlation between leakage current and temperature Rise for artificially aged insulators

인위적 열화 애자에 대한 누설전류와 온도와의 관계

  • Published : 2001.05.11

Abstract

In this study, the correlation between leakage currents and temperature rise was investigated for the more accurate diagnosis of bad insulator by use of the infrared camera. For the purpose, leakage currents and thermal images were measured for the artificially aged insulators using salt fog. From the results, it is concluded as follows ; in case of artificially aged insulators, the leakage. current was decreased with the duration of voltage application and was largely affected by humidity, which seems due to ionic conduction. Also, the correlation between temperature rise and leakage current was appeared to be quite linear, although it showed below linearity at large leakage current.

Keywords