A Study on the Technology Applying the Acoustic Wave Measurement to Diagnosing Particles in 800kV GIS

800kV GIS 이물진단을 위한 초음파 측정 적용기술연구

  • Published : 2001.11.03

Abstract

This paper described the outputs of acoustic sensors due to the vibration of particles in the mock up GIS. We used the two type of acoustic sensors which had 150kHz resonant frequency and 60kHz resonant frequency respectively. In the experiment of the mock up GIS we paid attention to the relationship between applied voltages and sensor outputs due to particles. In this results fall down voltages depended on the material and length of particles but lift off voltages depended on the materials of particles. And the sensors outputs were increased with applied voltages in the same particle.

Keywords