Dynamic change of frequency after a generator outage in an Interconnection considering the primary control

연계계통에서 발전기 정지에 따른 주파수의 동적 변화

  • Published : 2001.05.11

Abstract

Frequency is the unique physical value for all the interconnected systems. Therefore. the load frequency control is in the responsibility of all members in the interconnection power unbalance in one of the interconnected system can cause the problems in others. In the following text a brief description and the role of frequency in an interconnected system will be presented. Following is the short description of the Balkan Interconnection (UCTE Second Synchronous Zone) with schematic diagram. A Power-Frequency (P-f) dynamic model of a control area wil1 be shown. Model gives the analytical solution for frequency change versus a time after outage of a generator in the power system. This model will be applied to the Balkan Interconnection and compared with numerical approach. Advantages and drawbacks of the analytical method will be discussed Purpose of using this model is to investigate if the pumps in reversible hydropower plant will be underfrequency shed after the outage of the biggest generator unit in the interconnection, according %o (n-1) security postulate.