Abstract

The experiments were performed in model conductors under the application of ac and dc high-voltages. The results of an experimental investigation into the flashover characteristics of air dielectric strength in the presence of oil/gas flame are reported. It is demonstrated that flame can reduce by more than half, 80% in maximum the breakdown voltage of a model line. Taking a horizontal model line with a k=0.5, it can be seen from the results that the reduction of flashover levels, in comparison with the no-flame case, are 78.7[%] for h=0[cm], 59.6[%] for h=3[cm], 46.4[%] for h=6[cm], 40.4[%] for h=9[cm] and 23.2[%] for h=12[cm] when ac voltage is applied.

Keywords