Phase Selection Algorithm using Sequence Voltages for Transmission Line Protection

대칭분 전압을 이용한 송전선로 보호용 고장상 선택 알고리즘

  • Published : 2001.11.16

Abstract

A reliable fault type identification (phase selection) plays a very important role in transmission line protection, particularly in Extra High Voltage(EHV) networks. The conventional fault type identification algorithm used the phase difference between positive and negative sequence current excluding load current. But, it is difficult to pick out only fault current since we can not know when a fault occurs and identify the fault type in weak-infeed conditions that dominate zero-sequence current in phase current. The proposed algorithm can identify the accurately fault type using the sum of unit vectors which are calculated by positive-sequence votage and negative-sequence voltage.

Keywords