Overload Criterion of Mineral-Oil-Immersed Distribution Transformers Rated 100kVA and Less
100kVA 이하 유입식 배전용변압기의 과부하 판정기준 설정
- Yun, Sang-Yun (Soongsil Univ.) ;
- Kim, Jae-Chul (Soongsil Univ.) ;
- Lee, Young-Suk (Soongsil Univ.) ;
- Park, Chang-Ho (KEPRI) ;
- Shon, Hwa-Young (KERI)
- Published : 2001.11.16
Abstract
This paper covers general recommendations for top-oil temperature rising of mineral-oil-immersed power distribution transformer rated 100kVA and less, manufactured in Korea. In order to analyze the top-oil temperature rising due to the distribution transformer loading we performed experiments for oil-immersed distribution transformer, manufactured in domestic at KERI(Korea Electrical Research Institute) from December 2000 to May 2001. The magnitude of loading were changed, and the top-oil temperatures for each time were measured. Finally, we present the overload criteria of distribution transformer for summer and winter season in domestic. respectively.