The study of Method for the Diagnosis of Transformers Trouble

  • Published : 2001.10.01

Abstract

In this paper, we suggest a new distribution model for a single phase transformer which is different from the existing model which was modeled for only primary parts, but new distribution model is modeled for primary and secondary parts. Using this model, we simulate various faults of the transformer to know how the transfer function vary from the normal one, i.e., the trend of the variation of transfer function. As an another approach, we measure the voltage and current of a three phase transformer while various faults are made at the transformer. From the simulation of the model and experiment, we fine some trends of the variation of transfer function.

Keywords