아몰포스선을 이용한 전력선의 자계분포

Magnetic Field Distribution of Power Line Using Amorphous Wire

  • Moriyama, T. ;
  • Cho, M.W. ;
  • Hikita, M. ;
  • Hong, J.W. (Dept.of Electrical Engineering, Kwangwoon University)
  • 발행 : 2001.07.01

초록

To investigate the magnetic field distribution of power line, we used amorphous wire sensor. And we discuss extremely low frequency magnetic field distribution dependent upon arrangement of power line and shielding pipe made from iron or alumimum materials by both measurement and FEM(Finite Element Method) analysis. Appling current of single phase 60 [Hz] 15 [A] is supplied to copper wire coated enamel resign. As the results, we confirmed that linear characteristics of amorphous wire sensor is very excellent and measurement value agrees with FEM calculation. Magnetic field distribution due to shielding materials is changed by permeability and conductivity.

키워드