A Study on the Characteristics of Evaporative Heat Transfer for Carbon Dioxide in a Horizontal Tube

수평원관 내 이산화탄소의 증발열전달 특성 연구

  • 조은석 (서울대학교 대학원 기계공학과) ;
  • 윤석호 (서울대학교 대학원 기계공학과) ;
  • 김민수 (서울대학교 기계항공공학부)
  • Published : 2000.04.20

Abstract

Evaporative heat transfer characteristics of carbon dioxide has been investigated. Experiment has been carried out for seamless stainless steel tube with outer diameter of 9.55 mm and inner diameter of 7.75 mm. Direct heating method is used for supplying heat to the refrigerant was uniformly heated by electric current which was applied to the tube wall. The saturation temperature of refrigerant is calculated from the measured saturation pressure by using an equation of state. Inner wall temperature was calculated from measured outer wall temperature, accounting for heat generation in the tube and heat conduction through the tube wall. Mass Quality of refrigerant was calculated by considering energy balance in the preheater and the test section. Heat fluxes were set at 12, 16, 20, 23, and $27kW/m^2$, mass fluxes were controlled at 212, 318, 424, and $530 kg/m^2s$, and saturation temperature of refrigerant were adjusted at 0, 3.4, 6.7 and $10.5^{\circ}C$. From this study, heat transfer coefficients of carbon dioxide have been provided with respect to quality for several mass fluxes, heat fluxes. Finally, the experimental results in this study are compared with the correaltion by Gungor and Winterton(1987).