배전급 저항형 초전도 한류기의 전류제한특성에 대한 EMTDC 시뮬레이션

Simulation for current limiting characteristics of a resistive SFCL in the 22.9 kV distribution system

  • 발행 : 2000.08.16

초록

We simulated the current limiting characteristics of a resistive SFCL with 16 ${\Omega}$ of resistance for a single line-to-ground fault in the 22.9 kV system. The transient current during the fault increased up to 6.33 kA, 5.80 kA and 3.71 kA without SFCL at the fault angles of 0${\circ}$,45${\circ}$ and 90${\circ}$, respectively. An resistive SFCL limited the fault current to 2.27 kA in a half cycle. The quench resistance of 16 ${\Omega}$ was suggested to be appropriate to limit the fault current in the 22.9 kV distribution system.