Fault Location Algorithm for Parallel Transmission Line with a Teed Circuit

병행 2회선의 T분기 선로 고장점 표정 알고리즘

  • Published : 2000.11.25

Abstract

This paper presents a fault location algorithm for single-phase-to-ground faults on the teed circuit of a parallel transmission line. This algorithm uses only local end voltage and current information. Remote end and fault currents are calculated by using distribution factors. To reduce load current effect, negative sequence current is used. EMTP simulation result have shown effectiveness of the algorithm under various conditions.

Keywords