Automatic Measurement of the Degree of Contamination with Electric Conductivity and Oscillating Frequency

발진주파수 및 전도도를 통한 오손도 자동측정

  • Published : 2000.11.01

Abstract

To reduce the maintenance expense, and the possibility of electric outage and accident, we should optimize the outdoor insulation system. And for the optimization, accurate measurement for the degree of contamination with climatic conditions, such as wind, rain, and drought, should be carried. However the classical measuring method, brush wiping, has some problems in the aspect of man power, reliability, and expense. In this paper, we propose two type apparatus, which could detect the degree of contamination on insulators in outdoor insulation system, such as transmission and distribution line insulator and bushing. One use the leakage current, and the other use the oscillating frequency to check the degree of contamination. To avoid the oxidation of electrode AC source, and the low degree of contamination was applied. From the result of this investigation we could get the good relationship between the degree of contamination and the leakage current and oscillating frequency

Keywords