A Case Study on the vibration and noise by acoustic resonance in the tube bank of a boiler of 75MW power plant

75MW 급 발전용 보일러 관군에서의 음향공진에 의한 진동/소음 사례연구

  • 김철홍 (한국중공업(주) 기술연구원) ;
  • 방경보 (한국중공업(주) 기술연구원) ;
  • 주영호 (한국중공업(주) 기술연구원) ;
  • 변형현 (한국중공업(주) 기술연구원)
  • Published : 2000.11.16

Abstract

This paper presents phenomena of vibration and noise due to acoustic resonance in tube bank of a power plant. Acoustic resonance is may arise when the vortex shedding frequency coincides with the acoustic natural frequency. At the resonance, the value of vibration in this system was 595 ${\mu}m$, p-p and the sound pressure level was maximum 103 dBA. And the resonance frequency was found to be 35 Hz. When the difference of vortex shedding frequency and acoustic natural frequency is within ${\pm}20%$, acoustic resonance is possible. In this system, the difference of these frequencies was 1.8%. We can evaluate the possibility of acoustic resonance by using damping parameter. We did eliminate acoustic resonance by installing baffle in tube bank. After installing baffle, the level of vibration and noise was reduced dramatically.

Keywords