A Experimental Investigation on the PD Characteristics depending on the various Artificial Voids In Epoxy Insulator

에폭시 절연체의 보이드 크기에 따른 부분방전 특성연구

  • Published : 2000.07.17

Abstract

An experimental investigation has been performed in order to understand the $\Phi$-q-n characteristics related to the PD taking place from the various size of artificial defects inserted in epoxy insulation. In this purpose, PD has been detected simultaneously by two different methods such as commercialized PD detector(TE571) and our detection system using self designed CT type sensor. Under the presence of void in epoxy insulation, PD has been initiated at the voltages between 16kV and 20kV which are much lower than the dielectric strength of epoxy insulation (130kV/mm$\sim$l50kV/mm). And also it is revealed that $\Phi$-q-n characteristics have been observed to be dependent upon the size of the artificial defects. Throughout this work, the on site applicability of the self designed Sensor has also been proved by comparing the results with those from the commercialized PD detector. And more one, considerable basic data regarding the insulation, diagnosis could be provided to understand the presence of the voids possibly inserted into the epoxy insulation system of the power apparatus.

Keywords