The ageing process was checked by leakage current monitoring in Salt Fog Method. In order to monitor leakage current, DAS with 12-bit, 8-channel A/D converter was prepared. The monitored components of leakage current were averages of the rms and peak, max peak, cumulative charge, and the cumulative number of peak pulses. The acquired data were stored to the disc periodically. And, surface conductivity was measured to investigate loss of hydrophobicity. The results suggest that surface conductivity and leakage current are well corresponding to initial loss of hydrophobicity.