A Study on the Deteriorated Cause Analysis of Mold Type Potential Transformer

몰드형 계기용 변압기의 소손원인 해석에 관한 연구

  • Published : 2000.07.17

Abstract

In this paper, we intend to establish the judgement of electrical fire through analysis of PT(Potential Transformer) using the power installation. The columnar structure and the void generated by abrupt heat grew at the tenter of boundary-face on the metallurgical microscope analysis. The detection of OK lines was confirmed by EDX(Energy Dispersive X-ray spectroscopy) as melting and recombination due to the layer-short of the wiring. We found that the thermal-weight decrease occurred at 300$^{\circ}C$ in case of being the thermal-deterioration on the base of the result that analyzed the insulated-materials by using TGA, and the thermal reaction limited-value of PT insulator was about 300$^{\circ}C$ on the DSC curve. As this analysis, we confirmed what the layer-short appeared in the wiring of PT.

Keywords