Am EMTDC Analysis for Line Faults with a Superconducting Fault Current Limiter

초전도 한류기를 포함한 계통의 단락사고에 대한 EMTDC 해석

  • 최효상 (한전 전력연구원 전력계통연구실) ;
  • 황시돌 (한전 전력연구원 전력계통연구실) ;
  • 현옥배 (한전 전력연구원 전력계통연구실) ;
  • 정상진 (한전 전력연구원 전력계통연구실)
  • Published : 1999.02.01

Abstract

We have performed an EMTDC simulation for the current limiting effects of a superconducting fault current limiter (SFCL). The fault currents in the 154 kV transmission line between the Gaepo and Sungnam substations increased up to 54kA and 60kA during the line-to-line and three phase faults, respectively. The SFCL with 100 $\Omega$ of impedance after quench limited the currents to less than 17 kA within a half cycle. This limited current is well below the upper limit of a circuit breaker, suggesting that the impedance of the SFCL in the transmission line is sufficient.