An analysis of the measured electric and magnetic fields of transmission lines in Korea

전국의 송전선로 전자계 측정치와 계산치와의 비교 분석

  • Kim, S.B. (Korea Electric Power Research Institute) ;
  • Cho, S.B. (Korea Electric Power Research Institute) ;
  • Shin, K.Y. (Korea Electric Power Research Institute) ;
  • Lee, D.I. (Korea Electric Power Research Institute) ;
  • Kim, J.B. (Korea Electric Power Research Institute)
  • 김상범 (한국전력공사 전력연구원) ;
  • 조성배 (한국전력공사 전력연구원) ;
  • 신구용 (한국전력공사 전력연구원) ;
  • 이동일 (한국전력공사 전력연구원) ;
  • 김정부 (한국전력공사 전력연구원)
  • Published : 1999.07.19

Abstract

A nationwide survey for electric and magnetic fields(EMFs) near overhead transmission lines has been conducted. The median values of the electric and magnetic fields of 208 transmission lines were 0.50 kV/m and 12.6 mG, respectively. The maximum values were 3.16 kV/m and 125 mG. The measured EMFs were compared with the calculated ones. The causes of the discrepancy between measured and calculated EMFs are also discussed.

Keywords