양수발전기 고정자 권선에서 운전중 및 정지중 부분방전 특성

On-Line and Off-Line Partial Discharge Properties in the Pumped Storage Generator Stator Windings

  • Published : 1999.07.19

Abstract

Partial discharge(PD) tests were performed both when the pumped storage generator(rated 13.8kV and 220MVA) was on-line and off-line. This generator has been equipped with 12 bus coupler sensors in directional mode. PD tests were conducted using partial discharge analyzer(PDA), partial discharge meter(PDM) and digital partial discharge detector. PDA showed that the patterns of the normalized quantity number(NQN) and the partial discharge magnitude are in accord with on-line and off-line. The insulation condition was estimated by diagnostic tests(off-line) such as PD magnitude and dissipation factor.