TRV Characteristics of 345 kV GIS Circuit Breaker

345 kV급 GIS 차단기의 고유과도회복전압 특성 검토

  • 우정욱 (한국전력공사 전력연구원 전력계통연구실) ;
  • 심응보 (한국전력공사 전력연구원 전력계통연구실) ;
  • 강지원 (한국전력공사 전력연구원 전력계통연구실) ;
  • 강연욱 (한국전력공사 전력연구원 전력계통연구실)
  • Published : 1998.11.28

Abstract

The circuit breakers had been withdrawn from 345 kV SIC substation. because these were made following the old IEC requirement(IEC 56; TRV rating) and insufficient current rating(2,000 A) for the system requirement(4,000 A). And, they are going to be reused at 345 kV UR substation and SJS switching section. This paper deals with the TRV(temporary recovery voltage) analysis results in order to reuse them. The analysis results are satisfied with the IEC requirements of RRRV(Rate of Rise of Recovery Voltage) and peak voltage($U_c$) from 2000 to 2010.