A Study on Partial Discharge Measurement using Optical Fiber Sensors

광섬유 센서를 이용한 부분방전 측정연구

  • 이준호 (호서대학교 공과대학 전기공학과) ;
  • 이철규 (호서대학교 공과대학 전기공학과)
  • Published : 1998.11.28

Abstract

In this paper, an optical fiber sensor(OF sensor) utilizing the principal of Mach-Zehnder interferometer were proposed to detect the partial discharge signals in insulating oil. At first the AC breakdown signals were detected to check the response of the OF sensor. The detected signals from OF sensor was consistent with that from current probe. After the response checking, simultaneous measurements and continuous recording were made of electrical and the OF sensor signals from partial discharge(PD) produced by IEC(b) electrode system immersed in insulating oil. The continuous recording made it possible to extract basic quantities of PD from the OF sensor signals, such as pulse phase and pulse amplitude distribution. Through the signal analysis, the absolute peaks of the OF sensor PD signal was found to be increased with the amplitude of electrical signals, and these results mean that there is a strong correlation between OF sensor and electrical PD signals. It was demonstrated that the OF sensor in this research had a possibility to detect the PD signals in power apparatus.

Keywords