A Study on the high voltage measurement method using piezoelectric transformer type-actuator

압전 트랜스포머형 액츄에이터를 사용한 고전압 계측 방법에 관한 연구

  • Published : 1998.06.01

Abstract

In this paper, we used the $BaTiO_3$ system ceramics with high temperature stability for high voltage devision, and rosen type-piezoelectric transformer for high voltage measurement. when Line-high voltage is 13,20O[V], Input voltage of piezoelectric transformer type-actuator is about 390CV1, and output voltage of it is 26.5FVI on the no-load. And also, temperature stability from >$-25^{\circ}C$ to >$50^{\circ}C$ is less than ${\pm}4.45%$

Keywords