Proceedings of the IEEK Conference (대한전자공학회:학술대회논문집)
- 1998.10a
- /
- Pages.819-822
- /
- 1998
A New Current Compensation Estimation Method For Single Phase Active Power Filter
단상 액티브 파워 필터를 위한 새로운 전류 보상 방법
Abstract
A new active power filter (APF) circuit with a current compesation estimation method is proposed. The current compensation estimation method replaces a current sensor with an estimating circuit and therefore reduces the implementation cost In addition, a simple control scheme, based on the energy balance concept, is adopted to control the voltage of a DC capacitor. Therefore energy change in the DC capacitor can be compensanted in the next cycle. Since a sampling technique is used, a larger DC capacitor voltage ripple can be permissible and a relatively smaller DC capacitor can be used. The proposed method has advantages of the reduction of one current sensor, low implementation cost, and fast transient responses. The theoretical analysis and simulation results are given. The proposed control method is successfully verified by computer simulation.
Keywords