Abstract

In this study, the change of concrete temperature, strain and thermal stress were measured by using the embedded type concrete gauges in tendon gallery wall of containment building. A finite element analysis was performed to clarify the thermal behavior of concrete. The analytic and test results were investigated to improve the validity of analytic method. According to the test results, concrete temperature, strain and thermal stress were strongly affected by measuring point and environment condition of member. And the thermal stress was developed in the member which was not demoulded at early ages. This is caused by the change of internal temperature and restrained condition. A finite element effectively interpreted the test results by estimating the concrete properties and the site condition.