ESTIMATION OF REQUIRED CAPACITY OF SHUNT TYPE ACTIVE POWER FILTER WITH A THYRISTOR CONVERTER LOAD

  • Jeong, Seung-Gi (Dept. of Electrical Engineering Kwangwoon University) ;
  • Kim, Dong-Ha (Dept. of Electrical Engineering Kwangwoon University)
  • Published : 1998.10.01

Abstract

The main drawback of parallel type active power filters (APF) is the large capacity required for harmonic compensation. This paper evaluates the APF capacity requirement of harmonic/reactive power compensation for thyristor converter load. Theoretically achievable maximum power factor under partial load is evaluated. And it is shown that the APF capacity can be considerably reduced while slightly sacrificing the filtering performance by deliberately limiting the peak current of the APF.