EMTDC Simulation for a Superconducting Fault Current Limiter in the Transmission Line

송전선로 고장에 대한 초전도 한류기의 EMTDC 해석

  • 최효상 (전력연구원 에너지환경고등연구소) ;
  • 현옥배 (전력연구원 에너지환경고등연구소) ;
  • 고태국 (연세대학교 전기공학과) ;
  • 김진중 (전력연구원 에너지환경고등연구소)
  • Published : 1998.07.20

Abstract

We have performed an EMTDC simulation for the current limiting effects of a superconducting fault current limiter (SFCL) for the 154 kV transmission line between the Gaepo and Sungnam substations. The fault current increased up to 39 kA during an artificial ground fault. The SFCL with 100 ${\Omega}$ impedance after quench limited the current to 15 kA within a half cycle. This limited current is well below the upper limit of a circuit breaker, suggesting that the impedance of the SFCL in the transmission line is sufficient.