The residual voltage properties of 6.6kV XLPE Cable

6.6kV XLPE Cable의 잔류 전압 특성

  • Lee, Chang-Hoon (School of Electrical and Electronic Engineering, Wonkwang University) ;
  • Oh, Jae-Hyung (School of Electrical and Electronic Engineering, Wonkwang University) ;
  • Wu, Guangning (School of Electrical and Electronic Engineering, Wonkwang University) ;
  • Park, Dae-Hee (School of Electrical and Electronic Engineering, Wonkwang University)
  • 이창훈 (원광대학교 전기전자공학부) ;
  • 오재형 (원광대학교 전기전자공학부) ;
  • 오광영 (원광대학교 전기전자공학부) ;
  • 박대희 (원광대학교 전기전자공학부)
  • Published : 1998.07.20

Abstract

In this paper, the study of influence of DC voltage and AC voltage on residual voltage of XLPE Cable was presented. In the former case, when the DC voltage of -10.0[kV] was applied to XLPE Cable for 0, 600, 1200, 1800[sec], time constants were 2139, 1416, 939, 488[sec] and resistivities were 930, 615.65, 408.26, 212.17[${\Omega}{\cdot}m$] respectively. In the latter case, when the AC voltage of 4 and 6[kV] was applied to the same Cable for 600[sec] after applying DC voltage of -5.0[kV] for 600[sec], time constants were 215, 275[sec] and resistivities were 93.48, 119.57[${\Omega}{\cdot}m$] respectively. In this experiments, measurement voltage, charging time and measurement time were -8.0[kV], 30[sec], 600[sec] respectively.