Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1997.11a
- /
- Pages.231-234
- /
- 1997
Improved Direct Method for Computing a Closest Voltage Collapse Point
최단전압붕괴점을 계산하는 개선된 직접법
- Nam, Hae-Kon (Dept. of Electrical Engineering, Chonnam National University) ;
- Song, Chung-Gi (Dept. of Electrical Engineering, Chonnam National University)
- Published : 1997.11.29
Abstract
This paper presents improved direct method for calculating the closest saddle node bifurcation (CSNB) point, which is also applicable to the selection of appropriate load shedding, reactive power compensation point detection. The proposed method reduced dimension of nonlinear equation compared with that of Dobson's direct method. The improved direct method, utilizing Newton Iterative method converges very quickly. But it diverges if the initial guess is not very close to CSNB. So the direct method is performed with the initial values obtained by carrying out the iterative method twice, which is considered most efficient at this time. Since sparsity techniques can be employed, this method is a good choice to a large scale system on-line application. Proposed method has been tested for 5-bus, New England 30-bus system.
Keywords