Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1997.07c
- /
- Pages.1015-1017
- /
- 1997
A Study on High Impedance Fault Detection Method Using Harmonic Components
고조파 성분을 이용한 고저항 지락 사고 검출 기법에 관한 연구
- Ryu, Chang-Wan (Dept. of Control & Inst. Eng. Kwangwoon Univ.) ;
- Shim, Jae-Chul (Dept. of Control & Inst. Eng. Kwangwoon Univ.) ;
- Yim, Hwa-Yeong (Dept. of Control & Inst. Eng. Kwangwoon Univ.)
- Published : 1997.07.21
Abstract
A high impedance fault on the multi-grounded three-phase four-wire distribution system can not be detected by conventional overcurrent sensing devices. In this paper, the neural network is used to detect high impedance faults. The proposed algorithm using back - propagation neural network is demonstrated by simulation with the staged fault test data. The harmonic components of current and the phase of voltage are used as the inputs of neural network. Results of the simulation can be used as a reference for the development of a high impedance fault detector.
Keywords