Selection of mother wavelet for Low Impedance Fault Detection

Low Impedance Fault 검출을 위한 최적 마더 웨이브렛의 선정

  • 변성현 (성균관대학교 전기공학과) ;
  • 김철환 (성균관대학교 전기공학과) ;
  • 김일동 (한국전력공사 전력연구원) ;
  • 한경남 (한국전력공사 전력연구원)
  • Published : 1997.07.21

Abstract

This paper introduces wavelets and shows that they may be efficient and useful for the detection of general faults in power system. The wavelet transform of a signal consists in measuring the "similarity" between the signal and a set of translated and scaled versions of a "mother wavelet". The "mother wavelet" is a chosen fast decaying oscillation function. A number of mother wavelet for signal analysis have been proposed and some of them are in use in fault detection. However, the performance of fault detection depend on used mother wavelet. In the present paper a comparative evaluation of different mother wavelets for low impedance fault detection is performed. The discussion is focused in well-known mother wavelet based wavelet transform. Several families of wavelets are used to analyse transient earth fault signals in a 345kV model system as generated by EMTP.

Keywords