Analysis of Voltage Sag on Power Distribution System

배전시스템센서의 순간전압강하 분석

  • Published : 1997.07.21

Abstract

In this paper, we analyze the voltage sag caused by reclosing on electric power distribution system. When a fault is on the electric system, a reclosing operation brings a voltage sag on the feeders which is supplied with a common substation transformer. By analyzing the fault wave-form measured in the field, it is showed that a voltage sag is in proportion to a fault current. Also, we propose an adaptive reclosing scheme. This scheme changes the number of reclosing as a function of the magnitude of a fault voltage and the fault type. As the proposed scheme is compared with conventional scheme in the side of voltage sag and permanent fault, it is verified that the proposed scheme is more effective than conventional scheme.

Keywords