Winding Deformation Measurement using Low-voltage Impulse Tester in Transformers

변압기에서 저압충격시험기를 이용한 권선변형 측정

  • Published : 1997.07.21

Abstract

We describe the characteristic of LVI test system and methods to detect the deformation of windings in the power transformers. As the front rise time of recurrent-surge generator pulse less than 1000ns and the peak value of pulse is about 500V, we have the good results of detecting winding deformation in the LVI test of transformer. And we discuss the application of LVI test method and the condition of RSG pulse through results of in one and three pole transformers under Lab. tests.

Keywords