Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1996.07c
- /
- Pages.1774-1777
- /
- 1996
A Possible diagnostic method of cable system using SI-PD measurement
충격파-부분방전(SI-PD) 시험방법을 이용한 케이블 진단에 관한 기초 연구
- Kim, J.T. (Dae Jin University) ;
- Koo, J.Y. (Han Yang University) ;
- Jang, E. (Han Yang University) ;
- Cho, Y.O. (Korea Insulator Co.) ;
- Kim, S.J. (KEPRI) ;
- Song, I.K. (KEPRI) ;
- Kim, J.Y. (KEPRI)
- 김정태 (대진대학교 전기공학과) ;
- 구자윤 (한양대학교 전기공학과) ;
- 장은 (한양대학교 전기공학과) ;
- 조연옥 (고려애자(주) 연구소) ;
- 김상준 (전력연구원 배전기술팀) ;
- 송일근 (전력연구원 배전기술팀) ;
- 김주용 (전력연구원 배전기술팀)
- Published : 1996.07.22
Abstract
In this paper, applicability of SI-PD(switching impulse - partial discharge) testing method was put on an attempt as a newly proposed diagnostic method for the underground distribution power cable system in Korea. For this purpose, SI-PD testing equipment was designed, and tests were performed using artificial needle-type defects integrated into the 22.9 kV CN/CV cables in drder to prove its reliability. As a result, arc noises, generated from spark gap, were considerably decreased by use of a pneumatic switch immersed into oil, and artificial needle-type defects were well detected with impulse voltage level under