Proceedings of the KIEE Conference (대한전기학회:학술대회논문집)
- 1995.11a
- /
- Pages.453-455
- /
- 1995
Characteristics of long-term operated Electrostatic airclean filter for air-conditioner
장시간사용(長時間使用)한 공조용(空調用) 전기집진(電氣集塵)필터의 특성(特性)
- Hong, Young-Ki (LG Electronics Inc. Living System Research Lab.) ;
- Kang, Kwang-Ok (LG Electronics Inc. Living System Research Lab.) ;
- Lee, Sung-Hwa (LG Electronics Inc. Living System Research Lab.) ;
- Son, Sang-Cheol (LG Electronics Inc. Living System Research Lab.)
- Published : 1995.11.18
Abstract
In electrostatic airclean filter, the collection efficiency defends on particle charge in the ionizer section. The effect of electrostatic airclean filter condition (deposition of dust, variation of corona discharge current) on corona discharge characteristics was well studied. However, it seems not to be studied on corona discharge characteristics of electrostatic airclean filter respect to contaminated electrode which is caused by practical use. In this paper, Long-term(60days) effects are studied experimentally by two methods. The one is ozone concentration, the other is collection efficiency. Generation of ozone level was increased but collection efficiency was slightly reduced in long-term used electrostatic airclean filter.
Keywords