Safety Review Experience of Computerized Logic System for YGN 3 and 4

  • Published : 1995.05.01

Abstract

This article presents safety review experience of microprocessor-based Interposing Logic System(ILS) of Engineering Safety Feature Actuation System(ESFAS). The ILS is the first application of computerized logic design to safety system in Korean nuclear power plants without verification of the system reliability by proven technology concept. As a result of evaluation for the ILS, Korea Institute of Nuclear Safety(KINS) concluded that the microprocessor-based ILS is not acceptable in some features detailed enough to defend against software common mode failures(CMF). Therefore, we required licensee to install hardwired interlock signal configuration and a Hardwired Backup Panel to control safety-related equipment. We believe that the microprocessor-based ILS with the hardwired backup panel and inter-connection of interlock signal by hardwired configuration will improve the plant safety.

Keywords