뇌충격 측정시스템의 비교시험에 의한 성능평가 - 전파 뇌충격전압 인가시 -

Performance Evaluations of the Lightning Impulse Voltage Measuring System by Intercomparative Test - in case of full lightning impulse voltage -

  • 발행 : 1995.07.20

초록

Lightning impulse voltage is essential to evaluate the insulation performance of electric power apparatus. Recently international standard(IEC-60) on high voltage measurement techniques are being revised. In the draft of this standard, a new calibration method is introduced and the accuracy of most industrial measuring systems is maintained by means of comparison test against the reference measuring systems. Intercomparison tests of dividers for lightning impulse measurement were carried out by KERI. The shielded resisitive divider with 700kV rating developed by KERI were done comparison test with PTB divider with 300kV rating which have the similar charateristics as that were circulated among the laboratories. This paper reports on the comparison test results with full lightning impulse voltages from 126kV to 240kV. It is demonstrated that KERI are capable of realizing the idea in the revision of the IEC standand, that is, to establish traceability.

키워드