발전기 권선에서의 신호전송 특성에 관한 연구

A Study on the Signal Propagation Characteristics of Generator Windings

  • 황돈하 (한국전기연구소 전력기기연구부) ;
  • 김진봉 (한국전기연구소 전력기기연구부) ;
  • 김용주 (한국전기연구소 전력기기연구부) ;
  • 박명수 (한전 기술연구원 전력연구실) ;
  • 김택수 (한전 기술연구원 전력연구실)
  • 발행 : 1995.07.20

초록

The detection and measurement of partial discharge activity prevalent in the solid insulating systems of high-voltage generator stator windings has, for many years, been a recognized method of assessing the insulation condition of such systems. Partial discharge activity occurs at sites of degradation within, or at the surface of, stator's insulation systems under high voltage stressing. However, partial discharge pulses suffer from attenuation and distortion when transmitted along windings, because of the complex L-C network between windings. The mode of transmission varies with the signal frequency and is dependant on the geometrical configurations of windings. This paper reports the investigated results of the signal propagation characteristics along the windings when both sinusoidal signals and simulated partial discharge pulses are injected at the various positions of stator windings within the 25 MVA, 11 kV hydro generator. The on-line identification technique of partial discharge location in generator windings is also proposed in this study.

키워드