The Effect on the Extension Distances of Beam-Column Joint with High and Low Strength Concrete

고강도와 보통강도 콘크리트를 사용한 보-기둥 접합부의 내민길이에 따른 구조적 거동

  • 이광수 (한양대 대학원 건축공학과) ;
  • 안종문 (한양대 대학원 건축공학과) ;
  • 문정일 (한양대 대학원 건축공학과) ;
  • 박희민 ((주)삼성종합건설 시험실,) ;
  • 장일영 ((주)삼성종합건설 기술연구소) ;
  • 신성우 ((주)한양대 건축공학과)
  • Published : 1992.04.01

Abstract

ACI318-89 Recommened that when the specified compressive strength of concrete in a column is greater than 1.4 times that specified for a floor system, top surface of the column concrete shall extend 2ft (600mm) into the slab from the face of column to avoid unexpected brittle failure. The major variables are extension distance, compressive strength of concrete (f'c), shear confinement ratio(Vs), and loading types. The test results showed that the load capacity of the specimen subjected to monotonic loading had more than that of the specimen subjected to one way cyclic loadings. The failure models of specimens under cyclic loading were concentrated at 5∼20cm apart region from beam-column joint face. Ducility index(μf) are increased with increasing of shear confinement ratio. The specimen with 2ft extension distance shows more ductility than specimen with lft extension distance.