Location of Partial Discharge in Oil Transformer by means of Ultrasonic measurement
초음파 측정에 의한 변압기내 부분방전 위치측정
- Kwak, H.R. (Soong Sil Univ.) ;
- Jeon, H.J. (Soong Sil Univ.) ;
- Kim, J.C. (Soong Sil Univ.) ;
- Hwang, S.J. (Soong Sil Univ.) ;
- Yoon, Y.H. (Soong Sil Univ.) ;
- Kwon, T.W. (Research Center KEPCO) ;
- Yoon, Y.B. (Research Center KEPCO)
- 곽희로 (숭실대학교 전기공학과) ;
- 전희종 (숭실대학교 전기공학과) ;
- 김재철 (숭실대학교 전기공학과) ;
- 황선주 (숭실대학교 전기공학과) ;
- 윤용한 (숭실대학교 전기공학과) ;
- 권태원 (한국전력 기술연구원) ;
- 윤용범 (한국전력 기술연구원)
- Published : 1991.11.22
Abstract
This paper described an instrument for the detection and geometric location of partial discharge(PD) sources in oil transformer. This instrument measures electric current pulse and ultrasonic pulse simultaneously in order to determine the geometric location of PD in transformer. Laboratory experiment systems are made for detection and location of PD in oil transformer. It was observed that there are effects of the barrier, such as insulation papers, silicon steel plate and actual transformer with location and detection of PD in model transformer. Through the laboratory actual test, it was clarified that this measurement device could be used satisfactorily for location of pd in oil transformer.